SOUKOU ELB-440V Earth Leakage Breaker Tester | Breaker voltage AC 100–440 V, leakage current 0–100 mA/1 A, 1 ms timing, de-energized and live testing
SOUKOUELB-440V
[ICANSTron] Genuine authorized SOUKOU product

SOUKOU ELB-440V Earth Leakage Breaker Tester | Breaker voltage AC 100–440 V, leakage current 0–100 mA/1 A, 1 ms timing, de-energized and live testing

SOUKOU ELB-440V Earth Leakage Breaker Tester: Also Tests AC 440 V Circuits Overview The ELB-440V is a dedicated earth leakage circuit breaker tester from Soukou Electric (SOUKOU). It can output its own breaker voltage of up to AC 440 V for de-energized testing, can also test on live circuits, and can test detectors such as earth leakage alarms. Val

Breaker voltage AC 100/200/230/415/440 V; de-energized and live testingLeakage current AC 0–100 mA/1 A; ±1% rdg ±10 dgtTimer 0–199.999 s (1 ms); tests earth leakage alarms; approx. 7 kg
Corporate reference price (excl. tax)
Price on request
E-invoice issued after payment
One-year manufacturer warranty
Chat with Us on LINE

Overview

SOUKOU ELB-440V Earth Leakage Breaker Tester: Also Tests AC 440 V Circuits

Overview

The ELB-440V is a dedicated earth leakage circuit breaker tester from Soukou Electric (SOUKOU). It can output its own breaker voltage of up to AC 440 V for de-energized testing, can also test on live circuits, and can test detectors such as earth leakage alarms. Values are held automatically when the breaker trips, and it can also measure circuit voltage.

Key Specifications

  • Power supply: AC100V ±10%, 50/60 Hz
  • Current output: AC 0–100 mA / 1 A; max. load impedance 20 / 2 Ω
  • Breaker voltage: AC 100 / 200 / 230 / 415 / 440 V; 200 VA (at breaker trip)
  • Current measurement: AC 0–100 mA / 1 A, resolution 0.1 / 1 mA, ±1% rdg ±10 dgt (10% of each range and above)
  • Voltage measurement: AC 0–500 V, resolution 1 V, ±1% rdg ±10 dgt
  • Timer: 0–199.999 s (1 ms), up to 1999.99 s (10 ms); ±0.01% rdg ±1 dgt ±5 ms ±Δt
  • Stop signal: Earth leakage breakers: 10 mA or more (100 mA range), 100 mA or more (1 A range); leakage detectors: automatic a/b contact detection
  • Dimensions and weight: 180 × 256 × 166 mm, approx. 7 kg

Applications

  • Operation testing of earth leakage breakers in plant facilities, substations and building power distribution.

Specifications per the Soukou Electric ELB-440V product page (retrieved 2026-10-22).

Specifications

Key specifications
Breaker voltage AC 100/200/230/415/440 V; de-energized and live testingLeakage current AC 0–100 mA/1 A; ±1% rdg ±10 dgtTimer 0–199.999 s (1 ms); tests earth leakage alarms; approx. 7 kg
Model
ELB-440V
Brand
SOUKOU
Purchasing
In stock, tax incl. / B2B formal quotation request (RFQ)
Warranty
One-year manufacturer warranty

Calibration

If your instrument needs periodic calibration, register the brand, model and calibration requirements on the calibration service page and we will send a separate quote.

Go to calibration service